AH-9315

Combination Smoke and Heat Detector

Combination Smoke and Heat Detector

  Characteristics
  • Multi-purpose Design: when there is smoke or heat during pre-fire period, field situation will vary due to different environments. This combination design is to ensure that the pre-fire confirmation will not be affected by varying environments.
  • Smoke gate has a special design to obscure the strong light effectively and allow smoke to come in easily. Water vapor will not gather on the insect guard screen to cause a false alarm.
  • Features an accumulated water discharger to eliminate leakage of water from the water pipes or ceiling which may leak into the detector and cause a false alarm.
  • This detector has passed strict quality control and repetitive testing, hence its quality is stable and highly reliable.

  Specifications
Model AH-9315
Type 2-wire 3-wire 4-wire
Alarm Contact N/A N/A 0.8A @30V DC 0.4A @125V AC
Voltage Range 12 ~ 30V DC
Alarm Current
@24V DC 470Ω
40mA 40mA 35mA
Standby Current 20 ~ 85μA (Loop response under 75μA)
Sensitivity Setting
@24V DC 470Ω
Comply to EN54
Thermal Setting 55oC
Ambient Temperature -10oC ~ +55oC
Material Fire-proof plastic
Dimensions (mm)
Dia. x H
111 x 50
Weight Aboaut 170g
Color White

  Effective alert area

Building Height Area Covered
Under 4M 150 M2
4 ~ 20M 75 M2

  Approval

  Download